Insurance Updated November 2026  •  7 min read  •  By Enisave Solutions
Handheld thermal imaging camera displaying an infrared image

The Insurance Industry's Position on Electrical Risk

Electrical faults are among the leading causes of major property losses in South African commercial and industrial facilities. PSG Insure’s review of 2025 named fire as one of the most financially damaging risks for local businesses and noted that many incidents were linked to electrical faults, aged wiring and overloaded systems. Insurers have responded by asking for documented inspection of electrical equipment, and thermographic inspection is a widely requested form of that documentation.

Santam, South Africa’s largest short-term insurer, runs a Preferred Supplier programme for thermographic surveys. Requirements at other carriers vary by policy type, property size and risk profile. The common expectation is an annual inspection by a qualified thermographer, with findings documented and corrective actions recorded. Your policy wording and your broker define the requirement that applies to you; a general article does not.

Annual

inspection frequency commonly expected by commercial underwriters

24 hrs

Enisave report turnaround — ready for insurer submission

P1–P4

Enisave severity classification, with corrective action stated per finding

Why Insurers Request Thermographic Surveys

The logic is straightforward. Electrical fires are largely preventable. The faults that cause them — loose terminations, overloaded circuits, failing breakers, phase imbalance — generally produce heat before they produce flame, and a thermographic inspection detects that heat. An insurer that asks for annual inspections reduces its own loss exposure while giving the policyholder a mechanism to catch and correct faults before they escalate.

From the insurer’s perspective, a facility with a current thermographic report and documented corrective actions is a lower risk than one without. That difference can be reflected in underwriting decisions, premium calculations and excess structures at renewal, although no provider can guarantee a premium outcome. Business interruption is part of the same calculation: a short outage triggered by an electrical fault can cost more than the physical damage.

What Insurers Typically Require

  • Annual inspection frequency — commonly within the previous 12 months. Higher-risk categories (continuous process operations, cold storage, data centres) may be asked for shorter intervals. For comparison, NFPA 70B (2023) sets 12 months as the maximum infrared inspection interval and six months for equipment in the poorest condition category; see our NFPA 70B article.
  • Live-load inspection — equipment energised and operating at or above 40% of rated load, or at the highest normal load available (the NETA convention). A survey of isolated or de-energised equipment does not meet this.
  • Qualified thermographer — certified, with calibrated equipment. Self-conducted surveys are commonly not accepted.
  • Structured report — thermal and visual image pairs per finding, temperature measurements, ΔT values, severity classification and specific corrective action recommendations.
  • Corrective action documentation — many underwriters want evidence that P1 and P2 findings were addressed, not merely identified.

Santam Preferred Supplier Status

Santam operates a Preferred Supplier programme for thermographic inspection. Enisave Solutions is a Santam Preferred Supplier, and our reports are accepted by Santam for risk compliance, underwriting and renewal purposes. If your Santam policy includes a thermographic inspection condition, a report from a Preferred Supplier is intended to satisfy it without a separate re-survey. Where your policy carries specific wording, confirm it with your broker.

What a supplier programme looks at

Supplier criteria are set by Santam and can change. In general they cover thermographer certification level and currency, camera capability and calibration status, survey methodology, report format and image quality, professional indemnity cover, and track record. Our thermographers hold Infrared Training Center (ITC) certification, and our reports cite SANS 10142-1 clauses where a finding relates to an installation requirement.

  • Claims support — after an electrical fire or equipment failure, a current report showing that a survey was done and findings were addressed is useful documentation for your claim.
  • Premium considerations — documented proactive maintenance is a positive underwriting factor. We cannot guarantee premium outcomes.
  • Other carriers — the Preferred Supplier designation is specific to Santam, but the standard it reflects (qualified thermographers, sound methodology, insurer-ready reporting) is what other commercial property insurers look for too. Our reports include a compliance summary designed for submission to any insurer or broker.

What a Compliant Report Contains

  • Executive summary of overall system condition and critical findings
  • Inspection methodology — equipment used, emissivity settings, load at time of inspection, ambient conditions
  • Side-by-side thermal and visual image pairs for every identified fault
  • Temperature measurements (°C) and ΔT against both a similar component under similar load and ambient air
  • P1–P4 severity classification per finding with specific corrective action
  • Thermographer credentials and equipment calibration reference

Our guide to reading a thermographic report explains each element and what to do with it.

What happens if you don't comply?

Failure to submit a required thermographic report can result in risk conditions being applied to your policy, a higher excess on electrical fire claims, or non-renewal. More critically, if a fire occurs and the insurer determines that a required inspection was not carried out, the claim may be disputed or declined, depending on the policy wording. The cost of a survey is a fraction of the excess on a commercial fire claim.

If Your Insurer Has Asked for a Report

  • Check the exact wording in your policy schedule or the insurer’s request, and ask your broker what scope, interval and report content are required.
  • Contact Enisave Solutions to schedule a survey; we advise on scope and timing.
  • Make sure the survey is carried out under normal operating load.
  • Submit the completed report, with its compliance summary, to your insurer or broker.
  • Address P1 and P2 findings immediately, keep dated evidence of the corrective action, and re-scan after repair.

Scheduling Around Your Renewal Date

The most common compliance failure is timing: policyholders discover the survey requirement at renewal with too little time to survey, repair and submit. Schedule your annual survey at least six weeks before your renewal date. That leaves room for the survey, the report, corrective action on critical findings and submission. If your site has a planned year-end outage, see how to time a survey around the December shutdown.

Santam Preferred Supplier

Schedule Your Insurance-Compliant Survey

ITC-certified thermographers. Reports within 24 hours. Serving KZN, Gauteng, Western Cape, and Eastern Cape.

Request a Survey Quote

Sources